Power Dissipation Calculator

Calculate real, apparent and reactive power for DC circuits, AC single-phase and three-phase systems, plus junction temperature from thermal resistance.

Ad placeholder (leaderboard)

Electrical power dissipation calculations appear across electronics design, industrial electrical engineering, HVAC sizing, EV charging and PCB layout. This calculator covers all four practical scenarios in a single tool: DC and resistive circuits, AC single-phase loads (as found in household and light-commercial installations), balanced three-phase systems (motors, distribution panels, industrial drives) and thermal/heatsink derating for semiconductor components.

How it works

DC and resistive circuits

For a purely resistive load — a heater element, a shunt resistor, a cable run — all three forms of Joule’s law give the same answer:

P = V × I (voltage times current) P = I² × R (current squared times resistance) P = V² / R (voltage squared divided by resistance)

Choose which quantity to solve for. The tool cross-checks the result against the other two formulae whenever resistance is provided, so you can instantly spot a data-entry error.

AC single-phase power triangle

For AC circuits with reactive loads (motors, transformers, fluorescent ballasts) the picture is more complex. The apparent power S (in volt-amperes, VA) is the product of RMS voltage and RMS current. Only the fraction that is in phase with the voltage does real work; that fraction is the real power P (in watts), related to S by the power factor: P = V · I · pf. The remaining component is the reactive power Q (in volt-amperes reactive, VAR):

Q = √(S² − P²)

The phase angle φ satisfies pf = cos(φ). A power factor near 1.0 means an efficient, mostly resistive load; a low power factor means the grid and wiring must carry more current than the load actually needs, raising losses and conductor sizes.

Balanced three-phase

In a balanced three-phase system the real power is:

P = √3 × V_LL × I_L × pf

where V_LL is the line-to-line voltage and I_L is the line current. Equivalently, using the line-to-neutral (phase) voltage V_LN = V_LL / √3:

P = 3 × V_LN × I_L × pf

The factor √3 ≈ 1.732 arises because the three phase voltages are 120° apart and do not simply add; their vector sum gives a line voltage √3 times larger than the phase voltage.

Thermal / heatsink derating

Once you know the dissipated power P (from any of the formulae above), the junction temperature model gives the operating temperature of a semiconductor die:

T_j = T_a + P × Rθ_JA

Rθ_JA is the junction-to-ambient thermal resistance in °C/W, found on the device datasheet. The calculator highlights junctions above 85 °C (amber warning) and above 125 °C (red — exceeds the typical silicon limit).

Worked example

A 230 V single-phase induction motor draws 8 A at a power factor of 0.82:

  • Apparent power: S = 230 × 8 = 1,840 VA
  • Real power: P = 1,840 × 0.82 = 1,509 W ≈ 1.51 kW
  • Reactive power: Q = √(1,840² − 1,509²) = 1,054 VAR
  • Phase angle: φ = arccos(0.82) ≈ 34.9°

The wiring and switchgear must be rated for 8 A (the apparent current), even though only 1.51 kW of real work is delivered. This is why industrial sites install power factor correction capacitors — the capacitive VAR cancels inductive VAR, reducing the line current and hence cable losses.

Formula reference

Circuit typeFormula
DC resistiveP = V · I = I² · R = V² / R
AC single-phaseP = V · I · pf; S = V · I; Q = √(S² − P²)
AC three-phase (line-line)P = √3 · V_LL · I_L · pf
AC three-phase (phase)P = 3 · V_LN · I_L · pf
Junction temperatureT_j = T_a + P · Rθ_JA
Power factorpf = P / S = cos(φ)