Wire Gauge (AWG) Calculator

AWG to diameter, ampacity with derating, and voltage drop for any run length.

Ad placeholder (leaderboard)

The AWG (American Wire Gauge) system is the North American standard for specifying the diameter of solid and stranded round wire. Despite its name suggesting a simple size number, AWG is a logarithmic scale — every 3-gauge decrease doubles the cross-sectional area, and every 6-gauge decrease doubles it again. This calculator exposes four practical tools in a single place: look up any gauge’s physical dimensions, reverse-engineer the nearest AWG from a known diameter, apply the correct NEC ampacity derating for your installation, and verify that a cable run stays within the recommended voltage-drop limits.

How it works

AWG to physical dimensions

The standard defines wire diameter with the closed-form expression:

d = 0.127 × 92^((36 − AWG) / 39) mm

From the diameter the calculator derives the cross-sectional area (A = π/4 × d²), the area in circular mils (d² × 10⁶ with d in inches), and the DC resistance per metre using material resistivity:

R/m = ρ / A

where ρ(copper) = 1.724 × 10⁻⁸ Ω·m and ρ(aluminium) = 2.65 × 10⁻⁸ Ω·m.

Ampacity and NEC derating

“Ampacity” is the maximum continuous current a conductor can carry before its insulation overheats. The NEC publishes base values in Table 310.15(B)(16) for three temperature ratings (60°C, 75°C, 90°C) and two conductor materials (copper, aluminium). The base value must then be derated for two real-world factors:

  • Ambient temperature — the NEC 310.15(B)(2) correction factors assume a 30°C baseline; higher ambients reduce allowable current.
  • Conduit fill — NEC 310.15(B)(3)(a) requires a derating when four or more current-carrying conductors share the same conduit, because the combined heat raises the effective operating temperature.

The derated ampacity = base × temperature factor × fill factor.

Voltage drop calculation

For a single-phase circuit, the full current flows out on one conductor and returns on the other, so the effective resistive length is twice the one-way run:

V_drop = 2 × L × I × ρ / A

For a balanced three-phase circuit the factor is √3 instead of 2:

V_drop = √3 × L × I × ρ / A

The percentage drop = V_drop / V_system × 100. The NEC recommends ≤ 3% for branch circuits and ≤ 5% for the combined feeder and branch.

Worked example

Scenario: You are running a 15 A, 120 V single-phase circuit in a residential garage. The panel is 25 m (82 ft) from the outlet. You plan to use AWG 14 copper wire in a conduit that already has 4 other circuits passing through it, and the garage can reach 40°C in summer.

Step 1 — Ampacity check (Ampacity tab):

  • AWG 14 copper, 60°C base ampacity = 15 A
  • Temperature correction (36–40°C) = 0.82 → 15 × 0.82 = 12.3 A
  • Conduit fill with 4–6 conductors = 0.80 → 12.3 × 0.80 = 9.8 A

Result: the derated ampacity is only 9.8 A — insufficient for a 15 A circuit. Upsize to AWG 12 (base 20 A → derated 13.1 A, marginal) or AWG 10 (base 30 A → derated 19.7 A, comfortable).

Step 2 — Voltage drop check (Voltage Drop tab) with AWG 10:

  • Current = 15 A, length = 25 m, system = 120 V, single-phase
  • V_drop = 2 × 25 × 15 × 1.724×10⁻⁸ / (5.261×10⁻⁶) ≈ 2.46 V (2.05%)

Result: well within the 3% NEC recommendation. AWG 10 is the right choice for this installation.

GaugeBase amp. (Cu 60°C)Derated (40°C, 4-6 conds)Volt drop 25 m / 15 A / 120 V
AWG 1415 A9.8 A4.6 V (3.8%)
AWG 1220 A13.1 A2.9 V (2.4%)
AWG 1030 A19.7 A1.8 V (1.5%)

All calculations run entirely in your browser — no data is sent to any server.